To make an adjustment to a setting in the control,
begin by selecting the “ADJUST” menu. To change
from the view menu to the adjust menu, simultaneous-
ly press and hold all three buttons for 1 second. The
menu name, “ADJUST” will be displayed in the menu
field.
The menu will automatically revert back to the view
menu after 20 seconds of keyboard inactivity. Then
scroll to the desired item using the scroll button. Fi-
nally, use the L or M button to make the adjustment.
In the absence of other information, the values pro-
vided in Tables Q, R and S should be used as default
settings.
36
Heater Sequence of Operation
If all limits are satisfied and there is a call for heat:
1. The heater pump is powered and begins circulat-
ing water through the heat exchanger.
2. The blower is powered and goes through a 15 sec-
ond prepurge beginning when air flow is proven by
closure of the blower suction air pressure switch.
3. The igniter is powered, and once proven, heats up
for 20 seconds.
4. The gas valve is then energized for a 4 second
trial for ignition period. Trial for ignition is fixed at
50% input. The heater is allowed to modulate once
flame is proven and the firing rate will adjust to
match the load based on the configuration and set-
tings of the temperature control or external input.
5. Once the heat demand is satisfied the gas valve
will close and the blower will run a 30 second post
purge. The heater pump will continue to circulate
water for 0 to 10 minutes depending on the pump
delay setting on the Raypak modulating tempera-
ture control.
Fig. 33: Modulating Temperature Control Display
Item Field
Displays an
abbreviated
name of the
selected item
Buttons
Selects
Menus,
Items and
adjusts
settings
{
Menu Field
Displays the current menu
Number Field
Displays the
current value of
the selected
item
Status Field
Displays the
current status
of the control’s
inputs, outputs
and operation
Rank Item Field Number Field Type Fault Description
0 E01 Err Error EEPROM error
1 FP Err Warning Flame proof warning
2 BOIL OUT SHr Error Boiler outlet sensor short
3 BOIL OUT OPn Error Boiler outlet sensor open
4 BOIL IN SHr Error Boiler inlet sensor short
5 BOIL IN OPn Error Boiler inlet sensor open
6 SUP SHr Error System sensor short
7 SUP OPn Error System sensor open
8 OUTDR SHr Error Outdoor sensor short
9 OUTDR OPn Error Outdoor sensor open
10 DHW SHr Error DHW sensor short
11 DHW OPn Error DHW sensor open
Table T: Error Codes