Mode 8 – This mode is used for remote control of the
heater. The Boil Max setting is the heater shutdown
temperature. The heater is enabled with a control sig-
nal ≥ 0.5 VDC. 0.5 VDC corresponds to minimum fire
an 10 VDC corresponds to 100% firing rate. The BOIL
MAX setting is the heater shutdown temperature.
Definitions
% OUT - Current percent modulation rate of heater.
BOIL DSGN - Design boiler water temperature used in
heat loss calculations.
BOIL MASS - This setting allows adjustment in the
field for high or low thermal masses; High thermal
mass (setting=3) provides slower reaction, lower ther-
mal mass (setting=1) provides faster reaction.
BOIL MAX - Highest outlet water temperature that the
control is allowed to use as a target temperature.
BOIL MIN - Lowest outlet water temperature that the
control is allowed to use as a target temperature.
BOIL ON - Accumulated runtime of heater (up to 999
hours, then resets to 0).
BOIL OUT - Actual heater outlet water temperature.
BOIL START - Starting boiler water temperature.
33
2-10 VDC 4-20 mA* Boiler Target
0 0 --- (OFF)
1 2 --- (OFF)
2 4 50°F
3 6 71.3°F
4 8 92.5°F
5 10 113.8°F
6 12 135°F
7 14 156.3°F
8 16 177.5°F
9 18 198.8°F
10 20 220°F
Table P: 2-10 VDC or 4-20 mA External Input Signal
*Requires a 500Ω resistor.
NOTE: The defined terms are not active in all
modes of control operation.
BOIL SUP - Actual system supply water temperature.
BOIL TARGET - Target temperature that the heater is
trying to maintain.
‘BURNER’ DELAY - Holds control output at ignition
setting from the start of the ignition sequence to the
specified burner delay time (0 to 3:00 min.).
DEM 1 - Indicates 24 VDC signal has been supplied to
the H+D terminal.
DEM 2 - Indicates 24 VDC Flame Proof signal is pres-
ent.
DIFF - The operating differential of the heater; The
heater outlet water temperature is allowed to rise
above the BOIL TARGET temperature by
1
⁄2 of this dif-
ferential before the heater shuts off. For example, if
the heater target temperature is set to 160°F (71°C)
and the differential is set to 10°F (5°C), on temperature
rise, the heater will shut off at 165°F (74°C). Once the
heater shuts off, it will not come on again until the tem-
perature falls to 155°F (68°C).
EXTERNAL INPUT SIGNAL – Selects external input
signal range (0-10VDC or 2-10VDC):
0-10VDC or 0-20 mA external input signal – When
the 0-10VDC signal is selected, an input voltage of 1
VDC corresponds to a boiler target temperature of
50°F (10°C). An input voltage of 10 VDC corresponds
to a boiler target temperature of 220°F (104°C). As the
voltage varies between 1 VDC and 10 VDC, the boiler
target temperature varies linearly between 50°F
(10°C) and 220°F (104°C) (refer to Table O). If a volt-
age below 0.5 VDC is received, the boiler target
temperature is displayed as “– – –” indicating that
there is no longer an internal heat demand. A 0-20 mA
signal can be converted to a 0-10 VDC signal by
installing a 500 Ω resistor on the external input signal
device’s terminals.
2-10VDC or 4-20 mA external input signal – When
the 2-10VDC signal is selected, an input voltage of 2
VDC corresponds to a boiler target temperature of
50°F (10°C). An input voltage of 10 VDC corresponds
to a boiler target temperature of 220°F (104°C). As the
voltage varies between 2 VDC and 10 VDC, the boiler
target temperature varies linearly between 50°F
(10°C) and 220°F (104°C) (refer to Table P). If a volt-
age below 1.5 VDC is received, the boiler target
temperature is displayed as “– – –” indicating that
there is no longer an internal heat demand. A 4-20 mA
signal can be converted to a 2-10 VDC signal by
installing a 500 Ω resistor on the external input signal
device’s terminals.
Comentarios a estos manuales