FP - Flame proof warning.
MODE - Operating mode of the heater.
OFFSET - The Offset setting allows the boiler target
temperature to be fine tuned to the external input sig-
nal. The control reads the external input signal and
converts this to a boiler target temperature. The Offset
setting is then added to the boiler target temperature.
OUTDR - Outdoor air temperature.
OUTDR DESIGN - Design outdoor air temperature
used in the heat loss calculation.
OUTDR START - Starting outdoor air temperature.
PUMP DLY - Sets the operating time of the pump once
the CFH is satisfied.
TANK - Current DHW tank temperature (Mode 3).
TANK DIFF - Storage tank differential (Mode 3).
TANK TARGET - Target temperature in the DHW
storage tank (Mode 3).
UNITS - Selects the temperature units to be displayed
(°F or °C).
Water Heater (WH1)
Item Modes Default Setting Range
Boil Target
2 140°F OFF, 70 to 190°F
3, 7 160°F OFF, 70 to 190°F
Boil Max 2, 3, 6, 7 180°F OFF, 120 to 190°F
Boil Min 2, 3, 7 135°F OFF, 80 to 180°F
‘Burner’ Delay All 0:00 min 0:00 to 3:00 min
Boil Mass All 1 (Low) 1 (Low), 2 (Med), 3 (High)
Diff 2, 3, 7 Auto Auto, 2 to 42°F
DHW Target 3 120°F OFF, 70 to 190°F
DHW Diff 3 5°F 2 to 10°F
‘Pump’ Dly All 3:00 min OFF, 0:20 to 9:55 min, ON
Units All °F °F or °C
Mode N/A 3 2, 3, 7
External Input Signal 7 2 to 10 VDC 2 to 10 VDC or 0 to 10 VDC
Offset 7 0°F -10°F to 10°F
Table S: Modulating Temperature Control Default Setpoints—Water Heater
WWSD - Selects the outdoor temperature that shuts
the heater off, no matter what the demand. NOTE: The
WWSD segment is displayed on the LCD.
Operation
The Raypak electronic temperature control uses a
Liquid Crystal Display (LCD) as a method of supply-
ing information. The LCD is used to setup and monitor
system operation by means of three push buttons
(Item, L and M) shown at the bottom of Fig. 33.
All items displayed by the control are organized into
two menus, the view menu and the adjust menu. The
active menu is displayed in the upper right hand side
of the display in the menu field. The default menu is
the view menu.
When the temperature control is powered up, the con-
trol turns on all segments in the display for 2 seconds,
then the software version is displayed for 2 seconds.
At the end of that 4 second period, the control enters
the normal operating mode and “VIEW” is displayed.
Pressing the scroll button “scrolls” through the dis-
played values in the “VIEW” menu.