Mode 7 – Designed for an external input signal with
primary/secondary piping. The external input signal
can be provided from a BMS, an EMS or a sequenc-
ing control. The external input signal changes the
boiler target according to a linear scale (see Tables O
& P). The control operates the boiler burner to main-
tain the boiler target at the remote system sensor. See
Fig. 32.
32
water is also controlled to the boiler target temperature
(factory default WH1 water heaters). See Fig. 30.
Mode 4 – Not recommended.
Mode 5 – Outdoor reset using primary/secondary pip-
ing. The heater is operated as in Mode 2. However, the
target temperature is based on outdoor reset. See Fig.
31.
Mode 6 – Not recommended.
*
Fig. 32: Mode 7 Primary/Secondary Piping with
External Target Temp
*
Fig. 31: Mode 5 Primary/Secondary Piping with
Outdoor Reset
0-10 VDC 0-20 mA* Boiler Target
0 0 --- (OFF)
1 2 50°F
2 4 68.9°F
3 6 87.8°F
4 8 106.7°F
5 10 125.6°F
6 12 144.1°F
7 14 163.3°F
8 16 182.2°F
9 18 201.1°F
10 20 220°F
Table O: 0-10 VDC or 0-20 mA External Input Signal
*Requires a 500Ω resistor.
ELECTRONIC
Fig. 30: Mode 3 Dedicated DHW
*Maximum 4 times the pipe diameter or 12”, whichever is less.
*Maximum 4 times the pipe diameter or 12”, whichever is less.