INSTALLATION & OPERATING
INSTRUCTIONS
CATALOG NO. 3400.54C Effective: 01-08-09 Replaces: 09-15-08 P/N 241317 Rev. 4
This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future
reference.
Models 504–2004
Types H, WH, P & WHP
L
W
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
WARNING: Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury, exposure to hazardous materials* or loss of
life. Review the information in this manual carefully. *This unit contains materials that
have been identified as carcinogenic, or possibly carcinogenic, to humans.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and
liquids or other combustible materials in the vicinity of this or any other appliance. To
do so may result in an explosion or fire.
Installation and service must be performed by a qualified installer, service agency or
the gas supplier.
California Hot Water Supply, Inc.
(800) 249-7244
1
Vista de pagina 0
1 2 3 4 5 6 ... 55 56

Indice de contenidos

Pagina 1 - INSTRUCTIONS

INSTALLATION & OPERATING INSTRUCTIONSCATALOG NO. 3400.54C Effective: 01-08-09 Replaces: 09-15-08 P/N 241317 Rev. 4This manual should be maintain

Pagina 2

U.S. Installations1Canadian Installations2AClearance above grade, veranda, porch, deck, or balcony1 ft (30 cm) 1 ft (30 cm)BClearance to window or doo

Pagina 3 - CONTENTS

Optional Construction Air FilterAn optional construction air filter is available for use.The filter should be removed after construction is fin-ished

Pagina 4 - WARNINGS

b. Where communicating with the outdoorsthrough horizontal ducts, each opening shallhave a minimum free area of 1 in.2per 2,000BTUH (1,100 mm2per kW)

Pagina 5 - BEFORE INSTALLATION

Relief Valve PipingTemperature & Pressure GaugeThe temperature and pressure gauge is shipped loosefor field installation and must be installed wit

Pagina 6 - Component Locations

longer needed and the bypass can be shut off. If thebypass is not shut off as the system heats up, the out-let temperature may continue to climb and t

Pagina 7 - GENERAL SAFETY

Table F: Heater Rates of Flow and Pressure DropsNote: Basis for minimum flow is ΔT. Basis for maximum flow is gpm.equipped with flow control valves o

Pagina 8 - INSTALLATION

Domestic Hot WaterWhen designing the water piping system for domestichot water applications, water hardness should be con-sidered. Table G indicates t

Pagina 9 - Indoor Units

increase the inlet water temperature to a minimum of105°F (40°C) for Pool Heater (P and WHP) versionsand 120°F (49°C) for Hydronic Heating (H7) orDome

Pagina 10

Pool/Spa Water ChemistryChemical imbalance can cause severe damage to thepool heater and associated equipment. Maintain thewater chemistry according

Pagina 11 - Conventional Combustion Air

Further advice should be obtained from your pool orspa builder, accredited pool shop, or chemical suppli-er for the correct levels for your water.Auto

Pagina 12 - Water Piping

Rev. 4 reflects the following: Changes to: Table J on page 20; Fig. 16 on page 21; the Heater Sequence of Operation sec-tion on page 36; the UDB Diagn

Pagina 13 - Cold Water Operation

• Safety wiring must be NEC Class 1.• Heater must be electrically grounded as requiredby the NEC.• In Canada, CSA C22. 1 C.E.C. Part 1.The MVB 504-150

Pagina 14 - Hydronic Heating

Check the power source:AC = 108 VAC Minimum, 132 VAC MAXAB = 108 VAC Minimum, 132 VAC MAXBC = <1 VAC MaximumMaking the Electrical ConnectionsRefer

Pagina 15 - Air-Separation/Expansion Tank

Field Wiring ConnectionVentingGeneralAppliance CategoriesHeaters are divided into four categories based on thepressure produced in the exhaust and the

Pagina 16 - Domestic Hot Water

1. Condensate can freeze on the vent cap. Frozencondensate on the vent cap can result in a blockedflue condition.2. Give special attention to the loca

Pagina 17 - 2 open position, and Valve

7. The vent terminal requires a 12 in. vent terminalclearance from the wall.8. Terminate vent at least 1 ft above grade, includingnormal snow line.9.

Pagina 18 - Pool/Spa Water Chemistry

Table L: Category I Vertical Venting1 Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for furtherdetails.

Pagina 19 - Gas Supply

Common VentingManifolds that connect more than one heater to a com-mon chimney must be sized to handle the combinedload. Consult available guides for

Pagina 20 - Electrical Power Connections

system. Turn on any exhaust fans, such as rangehoods and bathroom exhausts, at maximumspeed. Do not operate summer exhaust fan. Closefireplace dampers

Pagina 21 - Check the Power Source

• 75’ of straight flue pipe• 65’ of straight flue pipe and one elbow• 55’ of straight flue pipe and two elbows• 45’ of straight pipe and three elbowsT

Pagina 22 - Field Wiring Connection

* Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further details. ** Subtract 10 ft per elbow. Max. 4

Pagina 23

WARNINGS 4BEFORE INSTALLATION 5Product Receipt 5Model Identification 5Ratings and Certifications 5Installations at Elevation 5Component Locations 6Gen

Pagina 24 - Venting Configurations

Freeze ProtectionThe Raypak electronic temperature control includes afreeze protection feature. In the event the temperaturedrops below 40°F at any of

Pagina 25 - Fig. 20: Vertical Venting

maintain near 160ºF system supply temperature, andif the system ΔT is 10ºF, then the system return (target)set-point is 160-10=150ºF.Deadband: Deadban

Pagina 26

Mode 7 – Designed for an external input signal withprimary/secondary piping. The external input signalcan be provided from a BMS, an EMS or a sequenc-

Pagina 27 - Engineered Vent Systems

Mode 8 – This mode is used for remote control of theheater. The Boil Max setting is the heater shutdowntemperature. The heater is enabled with a contr

Pagina 28 - Direct Vent—Vertical

Table Q: Temperature Control Default Setpoints—Boiler Boiler (H7)Item Modes Default Setting RangeBoil Target2 140°F OFF, 70 to 220°F3 160°F OFF, 70 to

Pagina 29 - Outdoor Installation

FP - Flame proof warning.MODE - Operating mode of the heater.OFFSET - The Offset setting allows the boiler targettemperature to be fine tuned to the

Pagina 30 - Controls

To make an adjustment to a setting in the control,begin by selecting the “ADJUST” menu. To changefrom the view menu to the adjust menu, simultaneous-l

Pagina 31 - Operating Modes

Ignition ModuleWhen additional heat is needed, the combustion airblower starts to purge air from the combustion cham-ber for 15 seconds. On proof-of-a

Pagina 32 - ELECTRONIC

Modulating Temperature ControlThis heater is equipped with a Raypak modulatingtemperature control. Refer to information starting onpage 31 for informa

Pagina 33 - Definitions

Blocked Vent SwitchThis heater is equipped with a blocked vent pressureswitch to prevent the operation of the heater when toomuch of the vent is block

Pagina 34 - 7 0°F -10°F to 10°F

DANGER: Indicates the presence of immediate hazards which will cause severepersonal injury, death or substantial property damage if ignored.WARNING:In

Pagina 35 - Operation

WIRING DIAGRAM - Models H & WHCalifornia Hot Water Supply, Inc. (800) 249-724440

Pagina 36 - Heater Sequence of Operation

WIRING DIAGRAM - Models P & WHPCalifornia Hot Water Supply, Inc. (800) 249-724441

Pagina 37 - High Limit—Manual Reset

START-UPPre Start-upFilling System (Heating Boilers) Fill system with water. Purge all air from the system.Lower system pressure. Open valves for norm

Pagina 38 - Fig. 39: Low Water Cut-Off

Check Power SupplyWith multi-meter at incoming power, check voltagebetween:Hot - Common (≈120 VAC)Hot - Ground (≈120 VAC)Common - Ground (< 1 VAC)A

Pagina 39 - Air Pressure Switch

pressure should read per the values in Table X fornatural and propane gas.2. If the pressure reading differs by more than ± 0.2in. WC, STOP – Call the

Pagina 40 - Models H & WH

Leak Test Procedure: Dual-Seat GasValveProper leak testing requires three pressure test pointsin the gas train.Remove the access panel on the rear of

Pagina 41 - - Models P & WHP

for operation as outlined by manufacturer. Burnershould be operating and should go off when con-trols are tested. When safety devices are restored,bur

Pagina 42 - START-UP

d. Gas is on at the meter and the heater.e. Incoming dynamic gas pressure to the gasvalve is NOT less than 4.0 in. WC for naturalgas or propane gas.To

Pagina 43 - Start-Up

TROUBLESHOOTINGSte p 8 Ste p 7 Ste p 6 Ste p 9 Step 1 Step 2 Step 3 Step 4 Step 5 Is there a Call For Heat? Is Disable connection intact

Pagina 44 - Finishing

UDB Fault HistoryTo view the fault codes in the UDB history file:1. Press the UP or DOWN buttons on the membraneswitch for 2 seconds to access the fau

Pagina 45 - Post Start-Up Check

BEFORE INSTALLATIONRaypak strongly recommends that this manual be re-viewed thoroughly before installing your MVB heater.Please review the General Saf

Pagina 46 - OPERATION

densate management system or drain, as requiredby local codes.3. Check that area is free from combustible materi-als, gasoline, and other flammable va

Pagina 47 - To Turn Off Gas To Appliance

6. Perform leakage test on gas valves (See Fig. 46.)and procedure on page 46.7. Test air switch in accordance with manufacturer’sinstructions. (Turn p

Pagina 48

(b) EXEMPTIONS: The following equipment is exempt from248 CMR 5.08(2)(a)1 through 4:1. The equipment listed in Chapter 10 entitled "EquipmentNot

Pagina 49 - MAINTENANCE

LIMITED PARTS WARRANTY MVB – TYPES H AND WH MODELS 504-2004 SCOPE Raypak, Inc. (“Raypak”) warrants to the original owner that all parts of this heat

Pagina 50 - Schedule

LIMITED PARTS WARRANTY MVB – TYPES P & WHP MODELS 504–2004 SCOPERaypak, Inc. (“Raypak”) warrants to the original owner that all parts of this

Pagina 51 - APPENDIX

55START-UP CHECKLIST FOR FAN-ASSISTED RAYPAK PRODUCTS This start-up checklist is to be completely filled out by the service technician starting up the

Pagina 52

www.raypak.com Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468Litho in U.S.A.California Hot Water Supply, Inc.

Pagina 53 - MODELS 504-2004

General InformationTable A: Basic Data6Component LocationsPanels omitted for clarityFig. 1: Component Locations – SideTop panel, blower and gas train

Pagina 54 - MODELS 504–2004

GENERAL SAFETYTo meet commercial hot water use needs, the highlimit safety control on this water heater will shut off themain gas valve before the out

Pagina 55 - RAYPAK PRODUCTS

Equipment BaseThe heater should be mounted on a level, structurallysound surface. The heater is approved for installationon a combustible surface but

Pagina 56 - Litho in U.S.A

Fig. 5: Minimum Clearances from CombustibleSurfaces – Indoor and Outdoor Installationscodes and the requirments of the gas supplier. Threesides must b