Table F: Heater Rates of Flow and Pressure Drops
Note: Basis for minimum flow is ΔT. Basis for maximum flow is gpm.
equipped with flow control valves or other automatic
means to prevent gravity circulation of the heater
water during the cooling cycle. It is highly recommend-
ed that the piping be insulated.
Air-Separation/Expansion Tank
All heaters should be equipped with a properly sized
expansion tank and air separator fitting as shown in
Fig. 9.
Three-Way Valves
Three-way valves intended to regulate system water
temperatures by reducing flow in the boiler should not
be used. Raypak heaters are high-recovery, low-mass
heaters which are not subject to thermal shock. See
Fig. 14 and instructions on page 17 for adjusting the
manual bypass.
Fig. 9: Air-Separation/Expansion Tank
Fig. 10: Single Heater - Low-Temperature (Heat Pump)
Application with Primary/Secondary Piping
Fig. 11: Dual Heaters (Reverse/Return)
with Primary/Secondary Piping
Model
No.
Input Output 20° ΔT 30° ΔT 40° ΔT Min. Flow Max. Flow
MBTUH gpm ΔP gpm ΔP gpm ΔP gpm ΔP ΔT gpm ΔP ΔT
504 500 420 42 2.7 28 1.4 25 1.1 34 100 11.3 8
754 750 630 63 6.0 42 2.9 32 1.7 32 1.7 40 100 13.8 13
1104 1100 924 92 13.3 62 6.7 46 4.1 46 4.1 40 113 18.6 16
1504 1500 1260 84 13.3 63 8.0 63 8.0 40 113 22.2 22
2004 1999 1679 112 26.9 84 16.0 84 16.0 40 113 27.2 30
*Maximum 4 times the pipe diameter or 12”, whichever is less.
*Maximum 4 times the pipe diameter or 12”, whichever is less.