TempTracker mod+ Hybrid Installation and Operation Manual 9
HTC# 059105-00D

Two Setback modes are available for the TempTracker mod+ Hybrid:
• The Day/Night Scheduling provides an adjustable time-based schedule for the Setback (only available when Shutdown or Tstat is
selected as the Setback/Shutdown Startup option). See "Shutdown/Tstat/Setback Mode" on page 26.
• The Setback mode uses an external signal to switch the operation of the TempTracker mod+ Hybrid in and out of setback mode (only
available when Setback is selected as the Setback/Shutdown Startup option).

By connecting the control to the optional 4-20mA EMS Interface, the control shall be capable of accepting a remote set point.

An optional BACnet Interface Module (#651735) can be used to connect the control to a BACnet MSTP network for remote access.

If you need the TempTracker mod+ Hybrid to do additional tasks that either are not listed or do not know how to congure them,
contact your local Raypak representative.
Setting an Initial Program will ease the conguration of the TempTracker mod+ Hybrid and will give the opportunity to utilize many of
the energy saving features while giving comfortable heat when needed.
The program should consist of the following:
• Selecting the features that your system can utilize.
• Installation: Install the Control, switches and sensors. See"Installation" on page 10
• Setting the System Startup. See "Startup Settings" on page 20.
• Setting the System Operating Settings. See "Operating Settings" on page 31
• Setting the Stages. See "Modulating Boiler Operating Settings" on page 35. Also, see "Staging Boiler Operating Settings" on page 36
• Adjusting Reset Ratio and Water Offset (In Reset Mode Only). See "Reset Ratio" on page 31